Coils and turns
Definition
Primary coil
The input coil of a transformer, which is connected to the alternating supply.
Definition
Secondary coil
The output coil of a transformer, across which the changed alternating potential difference is produced.
- A transformer has two coils of insulated wire wrapped around a shared iron core.
- The primary coil is connected to the alternating supply, so it is the coil that power enters.
- The secondary coil is connected to the output circuit, so it is the coil that power leaves.
- Each coil is made of many loops of wire, and each complete loop is called one turn.
- The number of turns on the primary coil is written NpN_{\text{p}}Np and the number on the secondary coil is written NsN_{\text{s}}Ns.
- The potential difference across the primary coil is written VpV_{\text{p}}Vp and the one across the secondary coil is written VsV_{\text{s}}Vs.
The turns ratio equation
Definition
Turns ratio
The number of turns on the primary coil of a transformer compared with the number of turns on its secondary coil.
- The ratio of the two potential differences is equal to the ratio of the numbers of turns on the two coils.
- This is written as VpVs=NpNs\dfrac{V_{\text{p}}}{V_{\text{s}}} = \dfrac{N_{\text{p}}}{N_{\text{s}}}VsVp=NsNp, where both potential differences are in volts and the turns are plain numbers with no unit.
- If the secondary coil has more turns than the primary coil (Ns>NpN_{\text{s}} > N_{\text{p}}Ns>Np), the secondary potential difference is larger, so the transformer is step-up.
- If the secondary coil has fewer turns than the primary coil (Ns<NpN_{\text{s}} < N_{\text{p}}Ns<Np), the secondary potential difference is smaller, so the transformer is step-down.
- A secondary coil with 161616 times as many turns as the primary therefore gives a secondary potential difference 161616 times larger.
- Both potential differences must be in the same unit before you substitute, so either convert both to volts or keep both in kilovolts.
- Rearranging for the secondary potential difference gives Vs=Vp×NsNpV_{\text{s}} = V_{\text{p}} \times \dfrac{N_{\text{s}}}{N_{\text{p}}}Vs=Vp×NpNs.
Example
Finding the output of a grid transformer
- A power station transformer has 100010001000 turns on its primary coil and 16 00016\,00016000 turns on its secondary coil.
- The generators supply a primary potential difference of 25 000 V25\,000\ \text{V}25000 V.
- The secondary potential difference is 400 kV400\ \text{kV}400 kV, so this is a step-up transformer.
Power in a transformer
- A transformer that wastes no energy is described as 100%100\%100% efficient.
- In such a transformer, the power supplied to the primary coil equals the power delivered by the secondary coil, because energy is conserved.
- Power is potential difference multiplied by current, so this gives VpIp=VsIsV_{\text{p}} I_{\text{p}} = V_{\text{s}} I_{\text{s}}VpIp=VsIs.
- In this equation IpI_{\text{p}}Ip is the current in the primary coil and IsI_{\text{s}}Is is the current in the secondary coil, both in amperes.
- The product of potential difference and current stays the same, so if a transformer raises the potential difference by a factor, it lowers the current by the same factor.
- A step-up transformer with 161616 times as many secondary turns therefore gives 161616 times the potential difference and one sixteenth of the current.
- A step-down transformer does the reverse, lowering the potential difference and raising the current.
- Real grid transformers are slightly less than 100%100\%100% efficient, so their output power is a little smaller than their input power.
Example
Finding the current after stepping up
- The same transformer receives a primary current of 4000 A4000\ \text{A}4000 A at 25 000 V25\,000\ \text{V}25000 V and gives out 400 000 V400\,000\ \text{V}400000 V.
- Assume the transformer is 100%100\%100% efficient and rearrange the power equation for the secondary current.
- The power transferred is 25 000×4000=100 000 000 W25\,000 \times 4000 = 100\,000\,000\ \text{W}25000×4000=100000000 W on both sides of the transformer.
- The potential difference has risen by a factor of 161616 and the current has fallen by a factor of 161616.
Advantages of high-voltage transmission
- The power dissipated as heat in a transmission cable is P=I2RP = I^2 RP=I2R, so it depends on the square of the current.
- A step-up transformer that raises the potential difference by a factor nnn lowers the current by a factor nnn, which reduces the heating in the cables by a factor n2n^2n2.
- In the grid transformer above, the current falls by a factor of 161616, so the heating in the cables falls by a factor of 162=25616^2 = 256162=256.
- Less energy is dissipated, so more of the energy generated reaches consumers and the transmission is more efficient.
- Less fuel has to be burned to deliver the same energy to homes, which lowers costs and carbon dioxide emissions.
- A smaller current can be carried safely by thinner, lighter cables, which allows lighter pylons spaced further apart.
- The drawbacks are that transformers, tall pylons and long insulators are expensive, and a very high potential difference is dangerous, but the energy saved over the life of the grid outweighs these costs.
Example
Comparing cable losses before and after stepping up
- The 100 000 000 W100\,000\,000\ \text{W}100000000 W from the power station travels through cables with a total resistance of 4 Ω4\ \Omega4 Ω.
- Without stepping up, the current would be 4000 A4000\ \text{A}4000 A.
- Almost two-thirds of the power would be dissipated in the cables.
- After stepping up to 400 kV400\ \text{kV}400 kV, the current is 250 A250\ \text{A}250 A.
- Only 0.25%0.25\%0.25% of the power is now dissipated, which is 256256256 times less than before.
Common Mistake
- Do not put a primary value with a secondary value on the same side of the turns ratio equation, because each side must compare primary with secondary in the same order.
- Do not assume that a step-up transformer increases the power, because the current falls by the same factor as the potential difference rises.
- Do not mix kilovolts and volts in one calculation, because the answer will be wrong by a factor of 100010001000.
- Do not forget to square the current when you work out how much the heating in the cables changes.
Exam technique
Tackling transformer calculations
- Write down the equation you are using before you substitute, because the equation and the substitution often earn marks even if the final arithmetic slips.
- List the known values with labels such as VpV_{\text{p}}Vp, NsN_{\text{s}}Ns and IsI_{\text{s}}Is so that you cannot swap primary and secondary values.
- Use the turns ratio equation when the question gives numbers of turns, and the power equation when it gives currents.
- Check your answer makes sense, since a step-up transformer must give a larger potential difference and a smaller current than it receives.
- When asked why high-voltage transmission is better, link the smaller current to P=I2RP = I^2 RP=I2R and finish with less energy dissipated in the cables.
Self review
- State the equation that links the potential differences and numbers of turns of a transformer.
- Is a transformer with more turns on its secondary coil than on its primary coil step-up or step-down?
- State the equation that links the potential differences and currents of a 100%100\%100% efficient transformer.
- By what factor does the current change when a transformer raises the potential difference by a factor of 202020?
- Explain why reducing the current by a factor of 101010 reduces the heating in the cables by a factor of 100100100.